Technical date & dimensions
 Model
Parameter   LSB26 LSB34 LSB40 LSB49 LSB60 LSB73
Nominal refrigerating capacity Kw 26 34 40 49 60 73
Refrigerant              
Compressor Model   1000-AM-110 1000-AR-120 1500-AR-130 2000-AR-140 2500-AV-71 3000-AV-86
Rated power Kw 7.4 7.4 11.3 14.8 18.5 22
Evaporator Coolant   Water
Coolant outlet Temp. 7
Coolant inlet Temp. 12
Coolant flow flux M³/h 4.5 5.8 6.9 8.4 10.3 12.6
Coolant inlet/outlet caliber Inch 1 1/2" 2" 2.5"
Condenser Water inlet Temp. 30
Water outlet Temp. 35
Cold water flow flux M³/h 7.5 9 10.5 12.8 15.6 19
Cold water inlet/outlet caliber   1.5" 2" 2.5"
Power supply   380V/3N~/50Hz
Operation control method   Automatic
Safety protection device   Motor overload,high/low pressure,oil pressure difference,cooling water cut-off
Motor cooling method   Freon gas refrigeration(Environment-friendly refrigerant are also available)
Unit input power under rated operation condition Kw 7.56 8.56 11.76 15.12 18.72 22.41
Overall dimension(L*W*H) MM 1950X550X1500 2200X700X1600 2400X700X1600
Mounting dimension L*W MM 100X460 1100X500 1200X500
    Hole*Dia. MM 4-×¢20
                   
Parameter   LSB93 LSB107 LSB128 LSB145 LSB176  
Nominal refrigerating capacity Kw 93 107 128 145 176  
Refrigerant              
Compressor Model   3500-AW-106 4000-AW-129 5000-AW-154 5000-AZ-172 8000-AZ-205  
Rated power Kw 26 30 37 37 60  
Evaporator Coolant   Water  
Coolant outlet Temp. 7  
Coolant inlet Temp. 12  
Coolant flow flux M³/h 16 18.4 22 25 30.3  
Coolant inlet/outlet Temp 2.5" 3"  
Condenser Water inlet Temp. 30  
Water outlet Temp. 35  
Cold water flow flux M³/h 24 27.8 33.3 37.7 45.8  
Cold water inlet/outlet caliber   2.5" 3"  
Power supply   380V/3N~/50Hz  
Operation control method   Automatic  
Safety protection device   Motor overload,high/low pressure,oil pressure difference,cooling water cut-off  
Motor cooling method   Freon gas refrigeration(Environment-friendly refrigerant are also available)  
Unit input power under rated operation condition Kw 26.57 30.57 37.85 38.85 61.52  
Overall dimension(L*W*H) MM 2400X700X1600 3200X910X1800  
Mounting dimension L*W MM 1200X500 1500X650  
    Hole*Dia. MM     6-×¢20  